An inert gas system is only as good as its last proven reading. If the oxygen analyser drifts low, the deck seal runs dry or a trip is bridged, the cargo tanks look inerted while they slide back toward a flammable atmosphere. This guide covers the FSS Code limits, the checks inspectors run and the records that prove the barrier is real. Log IG readings and alarm tests free.

Tanker inert gas system

Inert gas system maintenance and inspection that proves every cargo tank stays below the line

Five numbers from FSS Code Chapter 15 define the barrier. Maintenance keeps them true; records let an inspector see they were true yesterday as well.

≤5%O2 in gas delivered
≤8%O2 in any part of a tank
125%of max discharge rate
100 mmWG low pressure alarm
2non-return devices

Inert gas system requirements under SOLAS and the FSS Code

Since 1 January 2016, SOLAS has required a fixed inert gas system on new oil tankers of 8,000 dwt and above carrying low-flashpoint cargo (previously 20,000 dwt), and on new chemical tankers carrying flammable cargoes. Chapter 15 of the FSS Code, as amended by MSC.367(93), sets what the system must do. For component-by-component upkeep, see our IG plant and nitrogen generator maintenance guide.

ItemFSS Code Chapter 15 requirementWhat an inspector looks for
Delivered gasNo more than 5% oxygen by volume at any required flow rate; gas above 5% vented to atmosphere automaticallyRecorder trace during the last cargo operation
Tank atmosphere8% oxygen or less in any part of the tank, at positive pressure in port and at sea, unless gas-freeTank readings logged before and during discharge
CapacityAt least 125% of the maximum cargo discharge rateDischarge rate kept within plant capacity
Non-return devicesAt least two, on deck in the cargo area: a deck seal or double block and bleed, then a non-return valve with positive closureSeal water level, valve condition, overhaul history
Deck water sealSupplied by two separate pumps; low level alarm at all times; protected from freezing; water loops on connected pipesBoth pumps proven, alarm tested, heating working
Indication and recordingOxygen content and main pressure forward of the non-return devices continuously shown and permanently recordedUnbroken records; pressure readout on the bridge
Pressure protectionSystem cannot exceed tank test pressure; tanks protected against over-pressure and vacuum when isolatedPV breaker and PV valves maintained and free
ManualsInstruction manual covering operation, safety, maintenance, health hazards and fault proceduresManual on board, crew familiar with fault actions

Why tanker inerting matters: the cargo tank explosion record

Hydrocarbon vapour cannot burn below about 11% oxygen. The FSS Code holds tanks at 8% to keep a margin, and the record shows what happens without that margin. See how oxygen readings are trended in a demo.

The oxygen ladder a tanker officer works with

5%IG delivered max
8%tank max
~11%will not burn below
19%IG space alarm



0%21% air
Inerted operating bandSafety marginFlammable if vapour present
88tank fire and explosion events on oil tankers over 80,000 dwt, 1980 to 2013, including 17 total losses (DNV GL study, 2017)
~Halfof the serious casualties in that study happened during repair and tank cleaning, not cargo handling
0 of 35chemical tanker incidents in a 2017 OCIMF review of 25 years occurred while an inert gas system was operating

Sources: J. Spouge, DNV GL, IChemE Hazards 27 (2017); OCIMF analysis as reported by the Nautical Institute (2023).

Inert gas alarms and trips inspectors test

Every alarm below is a FSS Code requirement, and every one is defeated more often by habit than by failure. A nuisance trip that is bridged rather than diagnosed is the quickest route from a working plant to an inspection finding. Schedule alarm function tests free.

All inert gas systems
  • Oxygen above 5% in the gas delivered
  • Pressure below 100 mm WG in the IG main
  • High gas pressure
  • Power failure to indicating devices or to automatic control
  • Low main pressure: independent alarm or automatic cargo pump stop
  • Oxygen below 19% in the IG equipment space, alarmed inside and outside
  • Deck seal low water level, active at all times
Flue gas and IG generator plants add
  • Low cooling or scrubbing water pressure or flow
  • High scrubber water level
  • High gas temperature
  • Blower failure
  • Insufficient fuel supply (IG generators)
Nitrogen generators add
  • Low feed-air pressure or flow, high air temperature
  • Electric heater failure and high condensate level

Oxygen analyser calibration and the IG record

The fixed analyser is the only witness to what went into the tanks, and the permanent record is the only way to call that witness later. A low-reading sensor is the dangerous failure, because everything looks fine. Pair the fixed unit with the handheld meters covered in our atmosphere testing and gas meter calibration guide.

01

Zero and span

Check against oxygen-free reference gas and fresh air at 20.9% on the maker's interval and before each cargo operation. Log the found and left values.

02

Cross-check

Compare the fixed reading with a calibrated handheld meter at the same sample point. A gap is a finding even when both read under 5%.

03

Sample line

A blocked filter or leaking line reads wrong however well the cell is calibrated. Inspect, drain and leak-test it with the cell.

04

Permanent record

Oxygen and main pressure must be permanently recorded. Check the recorder works, the clock is right and the files are kept.

Every calibration, alarm test and seal check behind one IG record

Found-and-left analyser values, trip tests, seal pump checks and PV breaker readings, logged on deck offline and ready for the vetting inspector.

Deck seal and PV breaker inspection checks

These are the two devices that stand between cargo vapour and the machinery space, and between the tanks and structural damage. Both are simple, both sit outside on deck, and both fail quietly. See deck checks with photo evidence in a demo.

Seal

Deck water seal

  • Water level correct and visible; low level alarm tested
  • Both supply pumps proven, not just the duty pump
  • Heating working in cold weather without boiling the seal
  • Water loops on drain, vent and sensing lines intact
  • Internals inspected for corrosion and demister fouling
PV

PV breaker and PV valves

  • PV breaker filled with the correct liquid to the correct level, checked with the main depressurised
  • PV valves lifting and seating freely, no corrosion or cargo residue
  • Flame screens and arrestors clean and intact
  • Settings recorded against the tank test pressure
  • Non-return valve overhauled and seating tight

Cargo tank atmosphere through the inerting cycle

The IG plant does different work at each stage of the cargo cycle, and each stage has its own target. Getting the purge wrong before gas freeing is how tanks pass through the flammable range. Our cargo tank cleaning guide covers the washing that sits between them.

Inert

Inerting

Displace air with inert gas until oxygen is 8% or less throughout the tank.

Hold

Topping up

Keep tanks at positive pressure at sea and in port; top up as pressure falls.

Purge

Purging

After washing, purge with inert gas until hydrocarbon is 2% or less by volume.

Free

Gas freeing

Ventilate to a steady 20.9% oxygen and no more than 1% LFL, plus toxic limits where relevant.

Purge and gas-freeing targets follow common tanker practice under ISGOTT. Use your SMS and the ship's cargo manual for the values that bind your operation.

IG system inspection: PSC, SIRE 2.0 and class

Three sets of eyes look at the same plant for different reasons. Prepare for all three with the same evidence, and see our SIRE 2.0 cargo and ballast chapter guide for the vetting side.

Port State Control

Findings are coded 07102 (inert gas system) and 08106 (inert gas alarm), with handheld meters under 06105 (atmosphere testing instrument). Expect a recorder check and an alarm demonstration.

SIRE 2.0 vetting

The inspector reviews records and asks the cargo officer to explain how the plant is run and what happens on an alarm. Hesitation about a bridged trip becomes a human-factors observation.

Class survey

The system is surveyed with the cargo installation: function tests, alarm and shutdown proof, and condition of seal, valves and scrubber.

Inert gas system inspection and maintenance schedule

Regulation sets what the system must do; the maker and the SMS set how often you prove it. The schedule keeps those sources apart.

TaskWhenBasis
Oxygen and pressure recorded while IG is suppliedContinuousFSS Code
Fixed analyser zero and span checkBefore each cargo operation, and per makerPractice
Handheld oxygen meters calibrated and bump-testedBefore each usePractice
Deck seal level checked; both pumps provenDaily in use; pumps per SMSPractice
Alarm and shutdown function testsBefore cargo operations, and per SMSPractice
PV breaker liquid level and conditionPer SMS, main depressurisedPractice
PV valves, flame screens and non-return valvePer makerMaker
Scrubber tower, demister and blowers inspectedPer makerMaker
Full system survey with function testsWith the class survey cycleClass

How Marine Inspection makes inert gas compliance provable

An inspector's questions rarely surprise anyone. The answers usually sit in a recorder file, a deck log, a calibration sheet and someone's memory. Marine Inspection puts each answer where it can be found in seconds. Build your IG evidence trail free.

What the inspector asks
Where the answer lives
"When was the analyser last calibrated, and what did it read?"
Calibration task with found and left values, dated and signed
"Show me the last alarm and shutdown test."
Function-test checklist per alarm, with photos of the panel
"Have both deck seal pumps been proven?"
Recurring task per pump, overdue items flagged to the office
"What happened with this high-oxygen trip?"
Defect raised to a work order, cause and fix recorded to closure
"When was the non-return valve last opened up?"
Maintenance history against the equipment, with findings

Inert gas system maintenance and inspection: FAQs

What oxygen level must inert gas be delivered at?

No more than 5% by volume at any required flow rate, under FSS Code Chapter 15. Gas above 5% must be vented to atmosphere automatically, not sent to the tanks.

What is the maximum oxygen in an inerted cargo tank?

8% by volume in any part of the tank, held at positive pressure in port and at sea, unless the tank has been gas-freed.

At what pressure does the IG low pressure alarm sound?

When pressure in the IG main falls below 100 mm water gauge. Low main pressure must also give an independent alarm or stop the cargo pumps automatically.

Which tankers need an inert gas system?

Oil tankers of 8,000 dwt and above carrying low-flashpoint cargo and chemical tankers carrying flammable cargo, keel-laid on or after 1 January 2016. Older oil tankers were covered from 20,000 dwt.

Why does the deck seal need two pumps?

The FSS Code requires two separate pumps so the seal keeps its water at all times; a seal that runs dry no longer stops cargo vapour flowing back toward the machinery space.

How should the oxygen analyser be checked?

Zero and span against reference gas and fresh air, cross-checked with a calibrated handheld meter, with the sample line inspected at the same time. See calibration records in a demo.

Inert gas, proven

Keep every tank below the line, and keep the proof

Analyser calibrations, alarm tests, seal and PV breaker checks and every high-oxygen event on one record, ready for PSC, class or the next SIRE 2.0 inspection.