Ship refrigeration maintenance keeps the provision rooms cold, the accommodation air conditioning working and the refrigerant where it belongs: inside the system. It covers compressor checks, condenser and evaporator care, refrigerant leak tests and the ODS and F-gas records that MARPOL Annex VI and, for EU-flagged ships, the EU F-gas rules require. Get it wrong and the cost is spoiled provisions far from port, a hot accommodation in the tropics, refrigerant vented to atmosphere and a record book that fails an inspection.

Engine room maintenance · for second and chief engineers

Cold rooms, cool cabins, no lost gas: running a ship’s reefer and AC plant without surprises

Compressor rounds, leak tests and refrigerant records in one routine that survives every crew change.

Free sign-up · Offline checklists at sea · Signed PDF records

1 Jan 2020HCFC installations prohibited on ships built on or after this date (MARPOL Annex VI Reg. 12)
kgODS Record Book entries are made in kilograms, promptly after each recharge, repair or release
5 t CO2eEU F-gas charge above which periodic leak checks apply
GWP 2,500EU limit for virgin refrigerant used to service larger systems since 2020

On most cargo ships the provision refrigeration plant is a small direct-expansion system with two compressors, a sea-water cooled condenser and evaporators in each cold room, sometimes sharing a condenser or compressor with the air conditioning. The AC plant is larger, running either direct expansion through an air handling unit or a chilled water loop. Both are usually looked after by the second or third engineer, and both are easy to neglect until something goes warm.

This guide follows the plant from the refrigeration cycle through the maintenance routine, compressor care, leak testing, records, troubleshooting and AC air handling. If you want the daily rounds and monthly leak checks on a phone checklist that works offline, you can start logging refrigeration tasks free.

How a ship refrigeration plant works, and where it fails

Every vapour-compression plant on board, from the provision rooms to the AC, runs the same four-stage cycle. Knowing where each stage fails makes fault-finding much faster.

1

Compressor

Raises refrigerant vapour to high pressure and temperature.

Fails by: worn valves, low oil, liquid slugging, belt slip
2

Condenser

Sea water or air removes heat; vapour condenses to liquid.

Fails by: fouled tubes, low sea water flow, air in the system
3

Expansion valve

Meters liquid into the evaporator and cuts its pressure.

Fails by: moisture freezing, blocked strainer, lost bulb charge
4

Evaporator

Liquid boils off, taking heat out of the room or air.

Fails by: ice build-up, failed defrost, fan faults

Driers, sight glasses, solenoid valves, oil separators and pressure switches sit around this loop and cause many of the day-to-day faults.

Ship refrigeration maintenance routine: daily to annual tasks

Set the exact tasks from the maker’s manual and your planned maintenance system. A typical routine for provision and AC plants looks like this:

TaskDailyWeeklyMonthlyYearly
Room temperatures and alarms checked
Suction, discharge and oil pressures logged
Sight glass: bubbles and moisture indicator
Compressor oil level and running noise
Evaporator ice and defrost operation
Cold room doors, seals and curtains
Leak check with electronic detector
Condenser sea water side and filters
AC filters, drains and fan belts
Safety cut-outs (HP, LP, oil) tested
Condenser tubes cleaned and inspected
Compressor oil changed, valves inspected

Typical practice, not a rule. Statutory leak-check intervals for EU-flagged ships depend on the charge size (see below). Plan the routine in a preventive maintenance schedule.

Reefer compressor maintenance: what to check and record

The compressor is the heart of the plant and the part most often blamed. Many compressor faults are really condenser, expansion valve or charge problems, so read the pressures before opening anything up. Each check below has a checkpoint type, so the record shows what was actually done.

Record

Pressures and temperatures

Suction, discharge and oil pressures, discharge temperature and room temperature, logged at the same time each day so trends show.

Visual

Oil level and colour

Level in the sight glass with the compressor running. Dark or foaming oil points to overheating or refrigerant in the crankcase.

Test

Safety cut-outs

High pressure, low pressure and oil pressure switches tripped at their set points and reset as the maker directs.

Measure

Superheat

Suction line temperature against saturation temperature. Too low risks liquid reaching the compressor; too high starves the evaporator.

Visual

Belts, couplings and mountings

Tension, wear and alignment on belt drives; vibration mountings and pipe supports for cracking.

Document

Overhaul findings

Valve plate, piston and bearing condition with photographs and parts used, against running hours.

Log every reefer reading, leak check and refrigerant top-up in one place

Readings that drift raise a job, and every kilogram of refrigerant added goes straight into the record.

Free to start · Works offline on board · Export to signed PDF

Refrigerant leak test on ships: methods and how often

Refrigerant leaks are the most common reefer fault and the most expensive to ignore: the plant loses capacity, the compressor works harder, and every kilogram lost is a release that has to be recorded. Use more than one method, because each finds different leaks.

Electronic detector

Handheld sniffer moved slowly along joints, valves and flare nuts. The routine method for monthly checks.

Best for routine checks

Soap solution

Bubbles pinpoint a leak the detector has narrowed down. Cheap and reliable on accessible joints.

Best for pinpointing

UV dye

Dye in the oil shows under a UV lamp. Useful for slow leaks in hard-to-reach places, if the maker allows dye.

Best for slow, hidden leaks

Pressure hold test

Dry nitrogen pressure held after repairs, watching the gauge over time. Proves the repair before recharging.

Best after repairs

EU F-gas leak-check intervals by charge size (without leak detection)

5 to 50 t CO2e
every 12 months
50 to 500 t CO2e
every 6 months
500 t CO2e and above
every 3 months

Intervals as summarised by Ireland’s EPA for the F-gas Regulation; a working leak detection system doubles each interval, and systems of 500 t CO2e or more need automatic leak detection. The regulation was replaced by Regulation (EU) 2024/573, so confirm current thresholds with your flag and refrigerant supplier.

F-gas record and ODS Record Book on ships: what the rules require

Two sets of rules decide what goes in the refrigerant records. MARPOL Annex VI applies worldwide; the EU F-gas rules apply to EU-flagged ships. For the wider Annex VI picture, see MARPOL compliance.

MARPOL Annex VI, Reg. 12Worldwide
  • Deliberate emissions of ozone-depleting substances prohibited
  • New installations containing HCFCs prohibited on ships built on or after 1 January 2020
  • Ships with rechargeable ODS systems keep an ODS Record Book, in a logbook or approved electronic system
  • Entries in kg for recharges, repairs, releases, discharges ashore and ODS supplied to the ship
Inspectors check: entries made promptly, quantities that add up, sealed systems correctly excluded.
EU F-gas rulesEU-flagged ships
  • Periodic leak checks on systems of 5 t CO2e or more
  • Since 1 January 2020, no virgin refrigerant with GWP of 2,500 or more to service systems of 40 t CO2e or more; recovered gas allowed until 2030
  • Records per system: gas type and quantity, leak-check dates, gas added, gas recovered
  • Labelling with gas type, charge and CO2e
West P&I’s summary: R-404A, R-507 and R-422D fall above the GWP limit.

The ODS points follow the Bahamas Maritime Authority’s notice on HCFC refrigerants; the F-gas points follow West P&I’s 2020 summary of the earlier F-gas Regulation. Older ships still running R-22 should plan a refrigerant change: supplies are getting scarcer and dearer.

Marine refrigeration troubleshooting: symptom, cause and fix

Start every diagnosis with the pressures, the sight glass and the room temperature. Together they usually point to one stage of the cycle.

SymptomLikely causeCheckFix
Room warm, low suction pressureShort of refrigerant, blocked drier or expansion valveSight glass bubbles, drier temperature difference, superheatFind and repair leak, renew drier, recharge and record
High discharge pressureFouled condenser, low sea water flow, air in systemSea water inlet and outlet temperatures, strainer, condenserClean condenser and strainer; purge non-condensables
Compressor short cyclingLow charge, LP switch set too close, iced evaporatorLP setting, evaporator, chargeCorrect setting, defrost, repair leak
Evaporator iced upDefrost heater or timer fault, door left open, fan faultDefrost cycle, heater current, door sealsRepair defrost, manual defrost, fix seals
Moisture indicator shows wetMoisture entered during repair or through a leakIndicator colour after runningRenew drier; evacuate and recharge if severe
Compressor noisy, oil foamingLiquid slugging, refrigerant in oil, worn partsSuperheat, crankcase heater, oil levelCorrect superheat, check heater, overhaul if worn
Compressor will not startSafety cut-out tripped, electrical faultWhich cut-out, motor and starterFind the trip cause before resetting

Marine AC plant maintenance: air handling, filters and drains

Marine air conditioning keeps accommodation liveable in the tropics, and the Maritime Labour Convention expects accommodation to be air conditioned except on ships regularly trading where the climate makes it unnecessary. Most AC complaints trace to a handful of problems on the air side.

ProblemClogged filters
FixClean or renew on a fixed interval; airflow and cooling both recover.
ProblemBlocked condensate drains
FixClear trays and drains; standing water breeds bacteria and causes damp cabins.
ProblemSlipping fan belts
FixCheck tension and wear monthly; low airflow looks like a refrigeration fault.
ProblemDirty cooling coils
FixClean coil fins; a fouled coil cuts capacity and can ice up.
ProblemUnbalanced air distribution
FixCheck dampers and cabin units before blaming the plant.
ProblemChilled water loop faults
FixCheck pump, expansion tank, air vents and water treatment where fitted.

Engine room AC and provision plants often share condensers and sea water pumps. For the wider engine room plan, see engine room maintenance.

How Marine Inspection supports ship refrigeration maintenance

Marine Inspection turns the refrigeration routine into checklists the crew complete on a phone, online or offline, with readings, photos and refrigerant quantities captured as they go.

On board, the problemWhat Marine Inspection does
Daily readings scribbled on a sheet nobody trends
Offline reefer rounds with pressures and temperatures logged against limits you set
Refrigerant added but the record book not filled in
Refrigerant entries in kg captured with the job, ready for the ODS or F-gas record
A slow leak noticed, then forgotten at crew change
Automatic work orders raised from a failed leak check and tracked to close-out
Leak-check due dates kept in someone’s head
Due-date alerts for leak checks, cut-out tests and annual overhauls
No proof of what was found during repairs
Photo evidence and signed PDF reports for the office, auditors and inspectors
Ratings unsure of the routine in English
Multi-language crew portal so everyone follows the same checklist

Plans scale from one ship to a fleet; see Marine Inspection pricing.

Ship refrigeration maintenance: keep it cold, keep it sealed, keep it recorded

Ship refrigeration maintenance comes down to reading the plant every day, finding leaks early, keeping the condenser and evaporators clean and recording every kilogram of refrigerant that goes in or comes out. Do that and the provision rooms stay cold, the cabins stay cool and the ODS and F-gas records stand up to any inspection. Keep the daily readings in a digital engine room logbook so the trend is there when you need it.

Stop losing refrigerant you never recorded

Daily reefer rounds, leak checks and refrigerant entries, logged on board and ready for every inspection.

Free sign-up · Offline at sea · Signed PDF reports

Ship refrigeration maintenance: frequently asked questions

How often should a ship’s refrigeration plant be leak tested?

Most ships leak check monthly as routine, plus after any repair. For EU-flagged ships, the F-gas rules set minimum intervals by charge size: every 12 months from 5 to 50 tonnes CO2 equivalent, every 6 months from 50 to 500, and every 3 months above 500, with intervals doubled where a leak detection system is fitted. Confirm current thresholds with your flag.

Does my ship need an ODS Record Book?

Yes, if it has rechargeable systems containing ozone-depleting substances. MARPOL Annex VI Regulation 12 requires an ODS Record Book, kept in a logbook or an approved electronic system. Entries in kilograms cover recharges, repairs, releases, discharges to reception facilities and ODS supplied to the ship. Ships with only permanently sealed systems do not need one.

Can I still use R-22 on board?

Existing R-22 systems installed before the cut-off can still be serviced, but new installations containing HCFCs such as R-22 are prohibited on ships built on or after 1 January 2020. Supplies are becoming scarcer and more expensive, so flag states such as the Bahamas recommend planning a change to another refrigerant to avoid operational disruption.

What does the EU F-gas Regulation mean for ships?

For EU-flagged ships, it means periodic leak checks on systems of 5 tonnes CO2 equivalent or more, records for each system and labelling. Since 2020, virgin refrigerants with a GWP of 2,500 or more, such as R-404A, may not be used to service larger systems, though recovered gas is allowed until 2030.

Why is my provision room warm when the compressor is running?

Usually because the plant is short of refrigerant, the evaporator is iced, or the condenser is fouled. Check the sight glass for bubbles, the suction and discharge pressures and the evaporator for ice. Low suction with bubbles points to a leak or blockage; high discharge points to the condenser or sea water flow.

How do you find a refrigerant leak on a ship?

Start with an electronic leak detector moved slowly along joints, valves and flare nuts, then pinpoint with soap solution. UV dye helps with slow leaks in awkward places where the maker allows it. After repairing, hold a dry nitrogen pressure test before evacuating and recharging, and record the refrigerant added.