An alarm system only works if people believe it. Every nuisance alarm that is silenced without a diagnosis teaches the watch to treat the next one the same way, and that is how real faults get missed on an unmanned night. For the Second Engineer, who usually owns the alarm and monitoring system, the job is to tell real alarms from false ones quickly, fix the cause, keep sensors calibrated and keep overrides under control. This guide gives a real-or-false triage, a cause library, calibration checks, rules for isolations, and the unmanned machinery space (UMS) dependencies. Start a free trial of Marine Inspection to log alarm faults and sensor checks per vessel.

ALARM PANEL
Every Alarm Is Either Telling the Truth or Teaching the Watch to Ignore It
Six lamps to recognise on any engine room panel. Only the first one is a real fault.
REAL
A true fault. Act first, then find why.
SENSOR
Reading drifts or sticks. Calibrate or replace.
WIRE BREAK
Loop open or shorted. Check the cable and terminals.
CHATTERING
Cycles on and off. Add delay or fix the cause.
STALE
Stays in alarm for days. Fix it or remove it.
OVERRIDDEN
Isolated or in manual. Must be logged.
Free trial available. Or book a walkthrough built around your own engine room.
BENCHMARK
Process industry guidance (EEMUA 191 and IEC 62682) gives a useful yardstick: under 1 alarm in 10 minutes in normal operation, under 10 alarms in the first 10 minutes of an upset, no chattering alarms and no unauthorised suppressions. These come from plant control rooms, not ship rules, so use them to judge your own alarm log rather than as a class requirement.
Real or False? Four Questions in Order
1
Does a second source agree? (another sensor, local gauge, trend)
YESTreat as real until proven otherwise
NOSuspect the sensor or its wiring
2
Does the real process value match the alarm?
YESGo to the process and fix the cause
NOGo to sensor, cable and terminals
3
Is the alarm cycling on and off?
YESChattering. Check delay, deadband and connections
NOA steady alarm. Check calibration and drift
4
Does it clear after a proper reset?
YESLog it and watch for repeat
NOTreat as a standing fault. Do not leave it overridden
A suggested triage order. Never assume a false alarm until a second source has been checked.
Alarm Health Targets: How Many Is Too Many
Alarms per 10 min, normal running

under 1
Alarms in first 10 min of an upset

under 10
Standing (stale) alarms

under 10
Shelved alarms

under 30
Chattering or fleeting alarms

0
Limits from the EEMUA 191 column of an IChemE alarm management guide. Bars are scaled to the largest limit (30), and the first row is drawn at a minimum width for visibility. Scale them to the size of your own alarm list.

The fastest way to find bad actors is a log you can sort. See how Marine Inspection tracks alarm faults by sensor and by vessel, so repeat offenders are obvious.

False Alarm Cause Library
Likely causeTypical signFirst checkUsual fix
Sensor drift or poor calibrationReading slowly moves away from a trusted gaugeCompare with a test gauge or referenceRecalibrate or replace, record as-found and as-left
Loose or corroded terminalAlarm comes and goes with vibrationCheck terminals and cable glandsClean, tighten, seal
Open or shorted loopReading jumps to an extreme value or the wire-break alarm lightsCheck the loop signal. A 4 to 20 mA loop reading far below 4 mA usually means a breakRepair the cable or replace the transmitter
Fouled or stuck sensorLevel or flow reading frozen or erraticInspect the float, probe or orificeClean or replace
Setpoint too tight, no delayAlarm on every manoeuvre or load changeReview the trend against the setpointAgree a change under management of change
Electrical noise or earth faultSeveral unrelated alarms togetherCheck earthing and screensFix the earth or screening
Power supply dipAlarm group trips at onceCheck the supply and the batteryRepair the supply, test the backup
Our summary of common causes, listed from the most frequent to the least. Specific values depend on your system, so follow the maker's manual.
Calibration Checks by Sensor Type
PRESSURE
Against a test gauge
Compare the transmitter with a calibrated test gauge at two or three points across the range.
TEMPERATURE
Against a reference
Check the probe against a reference thermometer in a bath or dry block, and check its cable resistance.
LEVEL
Against a known level
Check the switch or transmitter against the sight glass or a physical test of the float.
ALARM TRIP
Test the setpoint
Confirm the alarm actually trips at the set value, and that the delay time is as documented.
Record the as-found and as-left values and the date every time. Our suggested methods. Use the equipment maker's procedure and calibrated instruments.
Stop Chasing the Same Nuisance Alarm Twice
Log each false alarm with its cause and fix, so repeat alarms stand out and sensor checks have proof.
Free trial available. Or book a walkthrough built around your own engine room.
Overrides and Isolations: Do and Don't
DO
Log every isolation with the reason, the person and the time
Set a time limit and a plan to fix it
Tell the duty engineer and the Chief Engineer
Review all isolations at every handover
DON'T
Leave a detector isolated going into UMS
Leave an alarm in manual or repose condition
Change set values without approval and a record
Silence a repeat alarm without finding the cause
Pre-UMS checks in a Marine Insight guide say all alarms and safety cut-outs must be operational, no detectors isolated, none in manual mode and set values unmanipulated.
UMS Dependency: What Rests on the Alarm System
PERSONNEL ALARM
30 min
Maximum pre-set period
One Norwegian operating-arrangements checklist asks for a one-man watch alarm that activates after a pre-set time not above 30 minutes, with a three-minute pre-warning in the machinery space.
DEAD MAN TIMER
24 min
Typical reset interval
A Marine Insight guide describes resetting at intervals not above 24 minutes, with a bridge alarm if the timer is not reset within 15 minutes.
START OF UMS
Log
Record the commencement
Inform the duty officer, and record the start of UMS in the engine room log book.
Settings differ by class and flag. Both figures are examples from the two sources, not one rule. Check your class notation and the vessel's operating arrangements.
Alarm Log Review Routine
IntervalActionOutput
Every watchCheck for isolated or manual alarms, test lampsHandover note
WeeklySort the alarm log, list the ten most frequent alarmsBad actor list with an owner
MonthlyCheck standing and shelved alarms, review isolationsClean-up actions
Planned maintenanceCalibrate and function-test sensors and tripsAs-found and as-left records
Our suggested routine for a Second Engineer. Adjust it to the planned maintenance system and the Chief Engineer's standing orders.
How do I tell a false alarm from a real one?
Check a second source first. Compare the alarm with another sensor, a local gauge and the trend. If they agree, treat it as real. If not, suspect the sensor, its cable or its calibration.
How many alarms are acceptable?
Plant guidance (EEMUA 191) gives under 1 alarm in 10 minutes in normal operation and under 10 in the first 10 minutes of an upset. Ships have no single rule, so use these as a yardstick.
Can I isolate a nuisance alarm?
Only with a log entry, the right approval and a plan to fix it. Do not go into UMS with a detector isolated or an alarm in manual mode. Book a walkthrough of alarm and isolation logging to see it on a vessel.
How often should sensors be calibrated?
Follow the planned maintenance system and the maker's guidance, and class survey requirements. Record as-found and as-left values each time.
What is a chattering alarm?
An alarm that switches on and off repeatedly, often from a loose connection, noise or a signal near its setpoint with no delay or deadband. It should be fixed, not silenced.
Keep the Alarm System Something the Watch Can Trust
One trail for alarm faults, sensor calibrations and isolations across every vessel, so UMS depends on records, not memory.
Free trial available. Or book a walkthrough built around your own engine room.